Application
- Fire dampers with CE marking and declaration of performance, for the isolation of duct penetrations between two fire compartments in the event of a fire
- To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments
Special features
- Declaration of Performance according to the European Construction Products Regulation
- Classification according to EN 13501-3, up to EI 120 (ve, ho i ↔ o) S
- Certified mortar-based installation with reduced distances of 40 mm to load-bearing components or at least 10 mm between 2 fire dampers
- Surrounding gap dimensions in the mortar-based installation with mortar up to 225 mm permitted
- Meets the requirements of European product standard EN 15650
- Tested for fire resistance properties in accordance with EN 1366-2 (300 Pa and 500 Pa negative pressure)
- Meets the hygienic requirements according to VDI 6022-1, VDI 3803-1, DIN 1946-4, DIN EN 16798-3 as well as Ö-Norm H 6020 and H 6021 and SWKI
- Corrosion protection according to EN 15650 in connection with EN 60068-2-52
- Closed blade air leakage acc. to EN 1751, class 3
- Casing air leakage acc. to EN 1751, class C
- Low differential pressure and sound power level
- Any airflow direction
- Integration into the central BMS with TROXNETCOM
- Integration into the central building management system with the international standard fire damper system according to IEC 62026-2 with AS interface is possible
Classification
- Class of performance up to EI 120 (ve, ho, i ↔ o) S according to EN 13501-3
Nominal sizes
- 100, 125, 150, 160, 180, 200, 224, 250, 280, 315
- L: 400 mm
Variants
- With fusible link
- With spring return actuator
- With spring return actuator for use in potentially explosive atmospheres
- With cover grille on both sides as an upstream shutter for the air transfer unit
- With spring return actuator, duct smoke detector and cover grille on both sides as air transfer damper according to general building inspectorate licence Z-6.50-2516
For installation in Germany, please note: If a fire damper with only a mechanical shut-off element is to be used as an air transfer unit, the local building regulations apply. Such air transfer units are usually used in pressure differential systems only.
Parts and characteristics
- Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)
- Single-handed operation
- Installation orientations from 0° - 360
- Explosion-proof constructions for zones 1, 2, 21, 22
Attachments
- Limit switch for damper blade position indication
- Spring return actuator with 24 V AC/DC or 230 V AC supply voltage
- Spring return actuator for 24 – 230 V supply voltage, for use in potentially explosive atmospheres
- Network module for the integration with AS-i or LON networks
- Spring return actuator and pre-wired duct smoke detector with 230 V AC, 50/60 Hz or 24 V DC supply voltage for use as air transfer damper
- All attachments can also be retrofitted
Accessories
- Installation block ER for dry mortarless installation in solid walls and ceilings
- Installation kit TQ2 for dry mortarless installation in solid walls, in lightweight walls/fire walls with metal support structure and cladding on both sides, in shaft walls with and without metal stud frame, in timber stud, timber frame and solid timber walls as well as in solid timber ceilings, woodbeamed ceilings, and in combination with lightweight ceilings (ADK Modulraum system)
- Installation kit WA2 for dry mortarless installation in solid walls as well as in single-sided shaft walls with and without metal stud framing
- Installation kit WE2 for dry mortarless installation away from solid walls and ceilings as well as away from lightweight walls with metal stud frame cladding on both sides
- Installation kit GL2 for installation in lightweight partition walls/fire walls with flexible ceiling joint and for dry mortarless installation in lightweight partition walls with metal stud frame and cladding on both sides during wall construction
- Cover grilles
- Flexible connectors
- Extension piece
Useful additions
- Duct smoke detector RM-O-3-D
- Duct smoke detector with airflow monitor RM-O-VS-D
Construction features
- Rigid circular casing suitable for push fitting into cut circular holes without additional drilling and chiselling being required
- Spigot connections with lip seal on both ends, suitable for ventilation ducts according to EN 1506 and EN 13180 plus non-standard but commercial nominal sizes 180, 224 and 280
- Suitable for the connection of ducts, cover grilles or flexible connectors
- The release mechanism is accessible and can be tested from the outside
- One inspection access panel
- Remote control with spring return actuator
Standards and guidelines
- Construction Products Regulation
- EN 15650 Ventilation for buildings – Fire dampers
- EN 1366-2 Fire resistance tests for service installations – Fire dampers
- EN 13501-3 Fire classification of construction products and building elements
- EN 1751 Ventilation for buildings – Air terminal devices
- 2006/42/EC – Machinery Directive
- 2014/34/EU – ATEX Directive
Materials and surfaces
Casing:
- Galvanised sheet steel
- Galvanised sheet steel, powder-coated RAL 7001
- Stainless steel 1.4301
Damper blade:
- Special insulation material
- Special insulation material with impregnation
- Replaceable damper blade (from NS 180 mm)
Other components:
- Damper blade shaft made of galvanised steel or stainless steel
- Plastic plain bearings
- Elastomer seals
The design variants made of stainless steel or with powder-coated casings meet increased requirements for corrosion protection. Detailed resistance lists upon request.
Supply package
If attachments and accessories are factory-mounted on the fire dampers, they are already included in the order code. Depending on the installation situation, additional materials such as mortar, screws or mineral wool may be required for correct installation. Such materials are not usually included in the supply package (unless stated otherwise). Attachments and accessories have to be selected by people in charge of the building project. These people also have to select and provide any additionally required installation or fixing materials and make sure that the required classifications are met.
Maintenance
- The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later.
- A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
- Fire dampers must be included in the regular cleaning schedule for the ventilation system.
- For details on functional tests, maintenance and inspection refer to the installation and operating manual
Technical data
- Nominal sizes: 100 to 315 mm
- Casing length: 400 mm
- Volume flow rate range: up to 770 l/s (2770 m³/h)
- Differential pressure range: up to 1500 Pa
- Temperature range: -20 - 50 °C *
- Upstream velocity **: Standard version ≤ 8 m/s, version with spring return actuator ≤ 10 m/s, version with Ex actuator ExMax/RedMax-15-BF TR ≤ 10 m/s
* For FKRS-EU in Ex version, see supplementary operating instructions
** Data apply to uniform upstream and downstream conditions of the fire dampers
Correct use
- The fire damper is used as an automatic shut-off device to prevent fire and smoke from spreading through ducting.
- The fire damper is suitable for supply and extract air in HVAC systems.
- The fire damper may be used in areas with potentially explosive atmospheres if suitable special accessories are used with it and if the product bears the CE conformity marking according to Directive 2014/34/EU. Fire dampers for use in areas with potentially explosive atmospheres are marked for the zones for which they have been approved.
- Operation of fire dampers is allowed only in compliance with installation regulations and the technical data in the installation and operating manual.
- Modifying the fire damper or using replacement parts that have not been approved by TROX is not permitted.
Incorrect use:
- without specially approved attachments in areas with potentially explosive atmospheres
- as a smoke control damper
- outdoors without sufficient protection against the effects of weather
- in atmospheres where chemical reactions, whether planned or unplanned, may cause damage to the fire damper or lead to corrosion
For installation in Germany please note:
- Do not use it in extract air systems in commercial kitchens
- Do not use it as an air transfer damper
- Do not use it with a combined penetration seal
- Single installation in a sandwich panel wall is considered correct use. Do not combine it with cable penetrations
- Air transfer units may require a building inspectorate licence. This has to be determined and applied for on a case to case basis (by others).
- Flame-resistant building materials that form no dripping droplets (elastomer foams) have to be at least of fire rating class C - s2, d0 according to the German MVV TB (2019/1) guideline. The current national building regulations apply.