This specification text describes just one variant of the product and is suitable for many applications. Texts for other variants can be generated with our Easy Product Finder design program.
Rectangular VAV terminal units for variable and constant air volume systems, suitable for supply air, available in 6 nominal sizes. High control accuracy (even with upstream bend R = 1D).
Ready-to-commission unit which consists of the mechanical parts and the electronic control components. Each unit contains an averaging effective pressure sensor for volume flow rate measurement, a damper blade, and an integral sound attenuator. Factory-assembled control components complete with wiring and tubing. Effective pressure sensor with 3 mm measuring holes, hence resistant to contamination. Baffle plate is fitted after the damper blade for optimum acoustic and aerodynamic performance. Casing with acoustic and thermal insulation. Position of the damper blade indicated externally at shaft extension. The damper blade is factory set to open position, which allows a ventilation airflow even without control; this does not apply to variants with defined safe position NC
(normally closed). Meets the hygiene requirements of EN 16798, Part 3, of VDI 6022, Sheet 1, and of DIN 1946, Part 4.
- Integral attenuator with at least 26 dB insertion loss at 250 Hz
- Hygiene tested and certified
- Factory set-up or programming and aerodynamic function testing
- Parameters can also later be set on the control component; additional adjustment device may be necessary
- Inspection access according to VDI 6022
- Casing and damper blade made of galvanised sheet steel
- Damper blade seal made of TPE plastic
- Lining made of mineral wool
- Differential pressure sensor made of aluminium
- Plastic plain bearings
- Shaft and linkage: galvanised steel
Mineral wool:
- According to EN 13501, fire rating class A1, non-flammable
- RAL quality mark RAL-GZ 388
- Non-hazardous to health due to high biosolubility according to the German Hazardous Substance Ordinance and Note Q of European Regulation (EC) No. 1272/2008
- Faced with glass fibre fabric as protection against erosion from airflow velocities of up to 20 m/s
- Inert to fungal and bacterial growth
- Spigot with groove for double lip seal on the fan end, suitable for connecting ducts according to EN 1506 or EN 13180. Room end suitable for the connection of ducts.
- Declaration of hygiene conformity in accordance with VDI 6022, Part 1 (01/2018), ÖNORM H 6020 (02/2007) and ÖNORM H 6021 (09/2003)
- Meets the hygiene requirements according to EN 16798 Part 3, VDI 6022 Sheet 1, DIN 1946 Part 4
- Acoustic data to ÖNORM EN ISO 5135:1999
- Setting the volume flow without adjustment device via Vmin and Vmax potentiometers
- Electrical connections with screw terminals, no additional terminal box required
- The test report of the factory parameterisation, functional test and adjustment under air by reference measurement on a regularly validated test rig in accordance with DIN EN ISO 9001 is made available
- Nominal sizes: 125 to 400 mm
- Volume flow rate range: 14 – 1602 l/s or 50 – 5768 m³/h
- Minimum differential pressure: up to 123 Pa (without secondary silencer)
- Maximum differential pressure: 1000 Pa
- Closed blade air leakage to EN 1751, class 4 (nominal sizes 125 and 160, class 3).
- Casing air leakage to EN 1751, class 4 (nominal size 250, 315, 400, class B)
Specification text attachment
Variable volume flow control with electronic Easy controller to connect an external control signal; actual value signal can be integrated into the central BMS.
- Supply voltage 24 V AC/DC
- Signal voltages 0 – 10 V DC
- Possible override controls with external switches using voltfree contacts: CLOSED, OPEN, qᵥmin and qᵥmax
- Potentiometers with percentage scales to set the volume flow rates qᵥmin and qᵥmax without an adjustment device
- The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
- Volume flow rate control range: approx. 10 – 100 % of the nominal volume flow rate
- Clearly visible external indicator light for signalling the functions: Set, not set, and power failure
- Electrical connections with screw terminals
- Double terminals for looping the supply voltage, i.e. for the simple connection of voltage transmission to the next controller
Air-regenerated noise
Case-radiated noise
Order code for volume flow control (with Easy controller)
| TVZ | – | D | / | 160 | / | D1 | / | Easy |
| | | | | | | | | | | | | | |
| 1 | | 2 | | 3 | | 4 | | 5 |
| |
|
|
|
|
|
|
|
|
1 TypeTVZ VAV terminal unit, supply air
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Nominal size [mm]
125, 160, 200, 250, 315, 400
4 Accessories
No entry: none
D1 Double lip seal
5 Attachments (control component)
Easy Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers (provided on site)
Order example: TVZ-D/200/Easy| Acoustic cladding | With |
| Nominal size | 200 mm |
| Attachments (control components) | Easy volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers |