VAV terminal units control the volume flow in a closed loop, i.e. measurement – comparison – control.
The volume flow rate is determined by measuring the differential pressure (effective pressure). For this purpose the VAV terminal unit is fitted with a differential pressure sensor.
The static differential pressure transducer transforms the effective pressure into a voltage signal. The volume flow rate actual value is hence available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (Vnom).
The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS) or from switch contacts. Variable volume flow control results in a value between Vmin and Vmax. It is possible to override the room temperature control, e.g. by a complete shut-off of the duct.
The controller compares the volume flow rate setpoint value to the actual value and controls the actuator accordingly if there is a difference.
The volume flow rate parameters Vmin and Vmax are set on potentiometers (VRP) or stored in the controller. Voltage ranges are factory stored in the controller. Changes on the customer's site can easily be carried out using a potentiometer, an adjustment device or a notebook with service tool.
Volume flow control
Any attachments are to be defined with the order code of the VAV terminal unit.
Universal controller, static, for VAV terminal units, volume flow control
BP3 | M466EN6 | VRP-M | M546EJ1 | VFP-300 | M466EQ9 | NM24A-V-ST | ① ② ③ ⑤ ⑥ ⑦ ⑧ |
BP1 | M466EN6 | VRP-M | M546EJ1 | VFP-300 | M466ER0 | SM24A-V-ST | ④ |
BPB | M466EN6 | VRP-M | M546EJ1 | VFP-300 | M466DR2 | NF24A-V-ST spring return actuator | ① ② ③ ④ ⑤ ⑥ ⑦ |
BPG | M466EN6 | VRP-M | M546EJ1 | VFP-300 | M466EQ2 | LMQ24A-SRV-ST fast-running actuator | ① ⑥ ⑧ |
BPG | M466EN6 | VRP-M | M546EJ1 | VFP-300 | M466EQ3 | NMQ24A-SRV-ST fast-running actuator | ② ③ ④ ⑤ ⑦ |
BB3 | M546EG2 | VRP | M546EJ1 | VFP-300 | M466DJ8 | NM24A-V | ① ② ③ ⑤ ⑥ ⑦ ⑧ |
BB1 | M546EG2 | VRP | M546EJ1 | VFP-300 | M466DG8 | SM24A-V | ④ |
BBB | M546EG2 | VRP | M546EJ1 | VFP-300 | M466DR1 | NF24A-V spring return actuator | ① ② ③ ④ ⑤ ⑥ ⑦ |
XD1 | M546ED5 | GUAC-S3 | – | Included with GUAC-S3 | M466EL7 | 227-024-08-V | ① ② ③ ④ ⑤ ⑥ ⑦ |
XD3 | M546ED5 | GUAC-S3 | – | Included with GUAC-S3 | A00000051738 | 361C-024-20-V/ST07 spring return actuator | ① ② ③ ④ ⑤ ⑥ ⑦ |
① TVR, TVZ, TVA up to nominal size 250
② TVR, TVZ, TVA from nominal size 315
③ TVJ
④ TVT
⑤ TZ-Silenzio, TA-Silenzio
⑥ TVRK up to nominal size 250
⑦ TVRK from nominal size 315
⑧ TVLK
Universal controller, static, for VAV terminal units, differential pressure control
BR3 | M466EN6 | VRP-M | M546EJ6 | VFP-100 | M466EQ9 | NM24A-V-ST | ① ② ③ ⑤ ⑥ ⑦ ⑧ ⑨ |
BR1 | M466EN6 | VRP-M | M546EJ6 | VFP-100 | M466ER0 | SM24A-V-ST | ④ |
BRB | M466EN6 | VRP-M | M546EJ6 | VFP-100 | M466DR2 | NF24A-V-ST spring return actuator | ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ |
BRG | M466EN6 | VRP-M | M546EJ6 | VFP-100 | M466EQ2 | LMQ24A-SRV-ST fast-running actuator | ① ⑥ ⑧ |
BRG | M466EN6 | VRP-M | M546EJ6 | VFP-100 | M466EQ3 | NMQ24A-SRV-ST fast-running actuator | ② ⑤ ⑦ ⑨ |
BS3 | M466EN6 | VRP-M | M546EJ7 | VFP-600 | M466EQ9 | NM24A-V-ST | ① ② ③ ⑧ ⑨ |
BS1 | M466EN6 | VRP-M | M546EJ7 | VFP-600 | M466ER0 | SM24A-V-ST | ④ |
BSB | M466EN6 | VRP-M | M546EJ7 | VFP-600 | M466DR2 | NF24A-V-ST spring return actuator | ① ② ③ ④ ⑧ ⑨ |
BSG | M466EN6 | VRP-M | M546EJ7 | VFP-600 | M466EQ2 | LMQ24A-SRV-ST fast-running actuator | ① ⑧ |
BSG | M466EN6 | VRP-M | M546EJ7 | VFP-600 | M466EQ3 | NMQ24A-SRV-ST fast-running actuator | ② ③ ④ ⑨ |
BG3 | M546ED1 | VRP-STP | M546EJ6 | VFP-100 | M466DJ8 | NM24A-V | ① ② ③ ⑤ ⑥ ⑦ ⑧ ⑨ |
BG1 | M546ED1 | VRP-STP | M546EJ6 | VFP-100 | M466DG8 | SM24A-V | ④ |
BGB | M546ED1 | VRP-STP | M546EJ6 | VFP-100 | M466DR1 | NF24A-V spring return actuator | ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ |
BH3 | M546ED1 | VRP-STP | M546EJ7 | VFP-600 | M466DJ8 | NM24A-V | ① ② ③ ⑧ ⑨ |
BH1 | M546ED1 | VRP-STP | M546EJ7 | VFP-600 | M466DG8 | SM24A-V | ④ |
BHB | M546ED1 | VRP-STP | M546EJ7 | VFP-600 | M466DR1 | NF24A-V spring return actuator | ① ② ③ ④ ⑧ ⑨ |
XE1 | M546ED6 | GUAC-P1 | – | Included with GUAC-P1 | M466EL7 | 227-024-08-V | ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ |
XE3 | M546ED6 | GUAC-P1 | – | Included with GUAC-P1 | A00000051738 | 361C-024-20-V/ST07 spring return actuator | ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ |
XF1 | M546ED7 | GUAC-P6 | – | Included with GUAC-P6 | M466EL7 | 227-024-08-V | ① ② ③ ④ ⑧ ⑨ |
XF3 | M546ED7 | GUAC-P6 | – | Included with GUAC-P6 | A00000051738 | 361C-024-20-V/ST07 spring return actuator | ① ② ③ ④ ⑧ ⑨ |
① TVR up to nominal size 250
② TVR from nominal size 315
③ TVJ
④ TVT
⑤ TZ-Silenzio, TA-Silenzio
⑥ TVZ, TVA up to nominal size 250
⑦ TVZ, TVA from nominal size 315
⑧ TVRK up to nominal size 250
⑨ TVRK from nominal size 315
Any attachments must be defined with the order code of the VAV terminal unit.
Application
Construction
Volume flow controller VRP-M with static differential pressure transducer VFP-300
Signal voltage ranges
Operating modes
E: Single and M: Master
S: Slave operation
F: Constant value
Parameters are factory set. The customer defines the required operating mode and the volume flow rates in the order code at the time of ordering.
Commissioning
Volume flow and differential pressure controller VRP-M
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 10 % |
Power rating (AC) | including differential pressure transducer, without actuator max. 2.6 VA |
Power rating (DC) | including differential pressure transducer, without actuator max. 1.1 VA |
Setpoint value signal input | 0 – 10 V DC, Ra > 200 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Static differential pressure transducer VFP-300
Supply voltage | from the controller |
Measuring range | 0 – 300 Pa |
Linearity | ± 3 Pa |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Actuators NM24A-V and NM24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 3.5 W max. |
Torque | 10 Nm |
Running time for 90° | 150 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.710 kg |
Actuators SM24A-V and SM24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 4 W max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.910 kg |
Spring return actuators NF24A-V and NF24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 9 VA max. |
Power rating (DC) | 6.5 W max. |
Torque | 10 Nm |
Running time for 90° | 200 – 300 s |
Spring return time | < 20 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 1.91 kg |
Fast-running actuator LMQ24A-SRV-ST
Supply voltage | from controller VRP-M |
Power rating (AC) | 23 VA max. |
Power rating (DC) | 13 W max. |
Torque | 4 Nm |
Running time for 90° | 2.5 s |
Control signal | from controller VRP-M |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.810 kg |
Fast-running actuator NMQ24A-SRV-ST
Supply voltage | from controller VRP-M |
Power rating (AC) | 23 VA max. |
Power rating (DC) | 13 W max. |
Torque | 8 Nm |
Running time for 90° | 4 s |
Control signal | from controller VRP-M |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.970 kg |
Application
Construction
Volume flow controller VRP with static differential pressure transducer VFP-300
Signal voltage range
Operating modes
E2: Single and M2: Master
S2: Slave operation
F2: Constant value
Parameters are factory set. The customer defines the required operating mode and the volume flow rates in the order code at the time of ordering.
Commissioning
Volume flow controller VRP
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Power rating (AC) | without actuator max. 2.6 VA |
Setpoint value signal input | 2 – 10 V DC, Ra >100 kΩ |
Actual value signal output | 2 – 10 V DC linear, max. 0.5 mA |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Static differential pressure transducer VFP-300
Supply voltage | from the controller |
Measuring range | 0 – 300 Pa |
Linearity | ± 3 Pa |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Actuators NM24A-V and NM24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 3.5 W max. |
Torque | 10 Nm |
Running time for 90° | 150 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.710 kg |
Actuators SM24A-V and SM24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 4 W max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.910 kg |
Spring return actuators NF24A-V and NF24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 9 VA max. |
Power rating (DC) | 6.5 W max. |
Torque | 10 Nm |
Running time for 90° | 200 – 300 s |
Spring return time | < 20 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 1.91 kg |
Application
Construction
Volume flow controller GUAC-S3
Signal voltage ranges
Operating modes
E: Single and M: Master
S: Slave operation
F: Constant value
Parameters are factory set. The customer defines the required operating mode and the volume flow rates in the order code at the time of ordering.
Commissioning
Volume flow controller GUAC-S3
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | without actuator max. 1.2 VA |
Power rating (DC) | without actuator max. 0.6 W |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Actuator 227-024-08-V
Supply voltage | from the controller |
Power rating (AC) | 3 VA max. |
Power rating (DC) | 2 W max. |
Torque | 8 Nm |
Running time for 90° | 60 – 120 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 (cable entry at the bottom) |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.530 kg |
Spring return actuator 361C-024-20-V
Supply voltage | from the controller |
Power rating (AC) | 10 VA max. |
Power rating (DC) | 8 W max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Spring return time | < 15 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 (cable entry at the bottom) |
EC conformity | EMC according to 2014/30/EU |
Weight | 1.8 kg |
Functional description
The static differental pressure transducer transforms the differential pressure into a voltage signal. The differential pressure actual value is available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal differential pressure (Δpnom).
The differential pressure setpoint value is either a constant value or it comes from a setpoint adjuster or from switch contacts.
The controller compares the differential pressure setpoint value to the actual value and controls the actuator accordingly.
The differential pressure parameters are set on a potentiometer (VRP-STP) or stored in the controller. Voltage ranges are factory stored in the controller. Changes on the customer's site can easily be carried out using a potentiometer, an adjustment device or a notebook with service tool.
Constant pressure control
Variable pressure control
Application
Construction
Differential pressure controller VRP-M with static differential pressure transducer VFP-100
Volume flow controller VRP-M with static differential pressure transducer VFP-600
Signal voltage ranges
Operating modes
Factory settings are as follows: Differential pressure ∆pmin as ordered and for room pressure controllers the adequate ∆pnom. The effective pressure sensor of the VAV terminal unit is short circuited.
Commissioning
VRP-M
Constant pressure control
The differential pressure setpoint value as given in the order code is stored as Δpmin in the controller. The nominal differential pressure Δpnom is the reference unit.
To maximise the control accuracy, different pressure ranges with the corresponding nominal differential pressures are used. The correct range is factory set. It is possible to change Δpmin at a later stage but only within the factory set pressure range.
Variable pressure control
A setpoint value signal enables variable pressure control. The control range is Δpmin to Δpmax, based on the setpoint value signal 0 (2) – 10 V.
Volume flow and differential pressure controller VRP-M
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 10 % |
Power rating (AC) | including differential pressure transducer, without actuator max. 2.6 VA |
Power rating (DC) | including differential pressure transducer, without actuator max. 1.1 VA |
Setpoint value signal input | 0 – 10 V DC, Ra > 200 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Static differential pressure transducer VFP-100
Supply voltage | from the controller |
Measuring range | 0 – 100 Pa |
Linearity | ± 1 Pa |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Static differential pressure transducer VFP-600
Supply voltage | from the controller |
Measuring range | 0 – 600 Pa |
Linearity | ± 6 Pa |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Actuators NM24A-V and NM24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 3.5 W max. |
Torque | 10 Nm |
Running time for 90° | 150 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.710 kg |
Actuators SM24A-V and SM24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 4 W max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.910 kg |
Spring return actuators NF24A-V and NF24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 9 VA max. |
Power rating (DC) | 6.5 W max. |
Torque | 10 Nm |
Running time for 90° | 200 – 300 s |
Spring return time | < 20 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 1.91 kg |
Fast-running actuator LMQ24A-SRV-ST
Supply voltage | from controller VRP-M |
Power rating (AC) | 23 VA max. |
Power rating (DC) | 13 W max. |
Torque | 4 Nm |
Running time for 90° | 2.5 s |
Control signal | from controller VRP-M |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.810 kg |
Fast-running actuator NMQ24A-SRV-ST
Supply voltage | from controller VRP-M |
Power rating (AC) | 23 VA max. |
Power rating (DC) | 13 W max. |
Torque | 8 Nm |
Running time for 90° | 4 s |
Control signal | from controller VRP-M |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.970 kg |
VRP-M, Pressure ranges
VFP 100 | 2.5 | 30 | 80 | 100 |
VFP 100 | 2.5 | 15 | 40 | 50 |
VFP 100 | 2.5 | 7.5 | 20 | 25 |
VFP 600 | 15 | 180 | 480 | 600 |
VFP 600 | 7.5 | 90 | 240 | 300 |
① Min: Minimum value for ∆pmin and ∆pmax
② Max: Maximum value for ∆pmin and ∆pmax
Using a control signal also setpoint values < 30 % of Δpnom can be set. Pressure values smaller than Δplimit will be set to zero because they cannot be precisely controlled.
Application
Construction
Differential pressure controller VRP-STP with static differential pressure transducer VFP-100
Differential pressure controller VRP-STP with static differential pressure transducer VFP-600
Signal voltage ranges
Operating modes
Factory settings are as follows: Differential pressure ∆pmin as ordered and for room pressure controllers the adequate ∆pnom. The effective pressure sensor of the VAV terminal unit is short circuited.
Commissioning
VRP-STP
Constant pressure control
The differential pressure setpoint value that has been ordered (order code) is factory set as Δp in the controller. The nominal differential pressure Δpnom is the reference unit.
To maximise the control accuracy, different pressure ranges with the corresponding nominal differential pressures are used. The correct range is factory set. It is possible to change Δp at a later stage but only within the factory set pressure range.
Variable pressure control
A setpoint value signal enables variable pressure control. The control range is from Δplimit to Δpmax.
Differential pressure controller VRP-STP
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Power rating (AC) | including static differential pressure transducer, without actuator max. 2.6 VA |
Setpoint value signal input | 2 – 10 V DC, Ra >100 kΩ |
Actual value signal output | 2 – 10 V DC linear, max. 0.5 mA |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Static differential pressure transducer VFP-100
Supply voltage | from the controller |
Measuring range | 0 – 100 Pa |
Linearity | ± 1 Pa |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Static differential pressure transducer VFP-600
Supply voltage | from the controller |
Measuring range | 0 – 600 Pa |
Linearity | ± 6 Pa |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Actuators NM24A-V and NM24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 3.5 W max. |
Torque | 10 Nm |
Running time for 90° | 150 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.710 kg |
Actuators SM24A-V and SM24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 4 W max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.910 kg |
Spring return actuators NF24A-V and NF24A-V-ST
Supply voltage | from the controller |
Power rating (AC) | 9 VA max. |
Power rating (DC) | 6.5 W max. |
Torque | 10 Nm |
Running time for 90° | 200 – 300 s |
Spring return time | < 20 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC according to 2014/30/EU |
Weight | 1.91 kg |
VRP-STP, Pressure ranges
VFP 100 | 2.5 | 30 | 80 | 100 |
VFP 100 | 2.5 | 15 | 40 | 50 |
VFP 100 | 2.5 | 7.5 | 20 | 25 |
VFP 600 | 15 | 180 | 480 | 600 |
VFP 600 | 7.5 | 90 | 240 | 300 |
① Min: Minimum value (10 V) for ∆p
② Max: Maximum value (10 V) for ∆p
Using a control signal also setpoint values < 30 % of Δpnom can be set. Pressure values smaller than Δplimit will be set to zero because they cannot be precisely controlled.
Variable pressure control requires that the link between terminals 2 and 4 is removed.
Application
Construction
Volume flow controller GUAC-P1
Volume flow controller GUAC-P6
Signal voltage ranges
Operating modes
The required differential pressure is set at the factory. The effective pressure sensor of the VAV terminal unit is short circuited.
Commissioning
GUAC-P1, GUAC-P6
Constant pressure control
The differential pressure setpoint value as given in the order code is stored as Δpmin in the controller. The nominal differential pressure Δpnom is the reference unit.
To maximise the control accuracy, different pressure ranges with the corresponding nominal differential pressures are used. The correct range is factory set. It is possible to change Δpmin at a later stage but only within the factory set pressure range.
Variable pressure control
A setpoint value signal enables variable pressure control. The control range is Δpmin to Δpmax, based on the setpoint value signal 0 (2) – 10 V.
Differential pressure controller GUAC-P1
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | without actuator max. 1.2 VA |
Power rating (DC) | without actuator max. 0.6 W |
Measuring range | 0 – 100 Pa |
Linearity | ± 1 Pa |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Differential pressure controller GUAC-P6
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | without actuator max. 1.2 VA |
Power rating (DC) | without actuator max. 0.6 W |
Measuring range | 0 – 600 Pa |
Linearity | ± 6 Pa |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU |
Actuator 227-024-08-V
Supply voltage | from the controller |
Power rating (AC) | 3 VA max. |
Power rating (DC) | 2 W max. |
Torque | 8 Nm |
Running time for 90° | 60 – 120 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 (cable entry at the bottom) |
EC conformity | EMC according to 2014/30/EU |
Weight | 0.530 kg |
Spring return actuator 361C-024-20-V
Supply voltage | from the controller |
Power rating (AC) | 10 VA max. |
Power rating (DC) | 8 W max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Spring return time | < 15 s |
Control signal | from the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 (cable entry at the bottom) |
EC conformity | EMC according to 2014/30/EU |
Weight | 1.8 kg |
Condividi pagina
Consiglia questa pagina
Consiglia questa pagina inviando un link via e-mail.
Condividi pagina
Grazie per la tua condivisione!
La tua segnalazione è stata inviata e dovrebbe arrivare a breve.
Contatti
Siamo qui per te
Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +39 029829741 | Fax: +39 0298297460
Contatti
Grazie per il tuo messaggio!
Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +39 029829741 | Fax: +39 029829760
Contatti
Siamo qui per te
Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +39 029829741 | Fax: +39 0298297460
Contatti
Grazie per il tuo messaggio!
Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +39 029829741 | Fax: +39 029829760